Ambient Temperature Range
- -40° to 50° C (-40° to 122° F)
Applications
- Air Conditioning Systems
- Commercial & Mobile Refrigeration Systems, Refrigeration Appliances
- Heat Pump Systems
- Ice Cube Machines
- Liquid Coolers
Approvals & Certifications
- Low Voltage Directive (LVD) 2006/95/EC
- PED 97/23/CE A3.P3
- UL Recognized Component (Canadian & US)
Capacity
- Rated Capacity (Hot Gas): 0.73-13.97 KW
- Rated Capacity (Liquid): 1.40-20.10 KW
- Rated Capacity (Suction Vapor): 0.16-2.90 KW
Humidity
- 0 to 100 % Relative Humidity (0 to 97 % Relative Humidity, Non-Condensing for Below IPX5)
Materials of Construction
- Bi-Metallic Tube: Copper
- Bi-Metallic, Armature & ArmatureTube: Stainless Steel
- Pilot Plate: Thermoplastic (PEEK)
Maximum Opening Pressure Differential
- psi: 0.29 to 522 (kPa: 2 to 3,600, bar: 0.02 to 36)
Operating Pressure
- psi: 1,015 (kPa: 7,000, bar: 70) - Max.
Process Temperature
- 130° C (266° F) - Max.
- -40° to 105° C (-40° to 221° F)
Ring Material
- Solder Ring: Silver
- Support Ring: Teflon (PTFE)
Seat / Seal Material
- Seat Plate: Teflon (PTFE)
Spring Material
- Spring Wire Stainless Steel
Tube Connection
- 1/2” Tube
- 1/4” Tube
- 3/8” Tube