Ambient Temperature Range
- -40° to 65° C (-40° to 149° F)
Approvals & Certifications
- EN 60947-1
- EN 60947-4-1
- EN 60947-5-1
- CCC
- CE-Marked in Accordance with LVD 2006/95/EC
- GOST
- UL
BSP Connection
- G 1/2” A Male
- G 1/4” A Male
Cable Entry
- PG13.5 with Special Nut for 6 -14 mm Diameter Cables - Screwed
- PG16 for 8-16 mm Diameter Cables
- Rubber Cable Gland, 6 to 14 mm Diameter Cables
Capillary Length
- 6.56 to 16.4 feet (2 to 5 metres)
Diameter
- 0.37” (9.6 mm) - Sensor Pocket Internal Diameter
- 0.43” (11 mm) - Sensor Pocket External Diameter
Differential Pressure
- psi: 1.45 to 87.02 (kPa: 10 to 600, bar: 0.1 to 6)
Electrical Rating
- Contact Load, Silver: 10 A at 400 V (AC-15) for KP 35, KP 36 & KP 34, KP 35, KP 36, KP 37 Boiler Version
- Contact Load, Silver: 10 A at 440 V (AC-1) for KPI 35, KPI 36, KPI 38
- Contact Load, Silver: 12 W at 220 V (DC-13) for KP 35, KP 36, KPI 35, KPI 36, KPI 38 & KP 34, KP 35, KP 36, KP 37 Boiler Version
- Contact Load, Silver: 16 A at 400 V (AC-1, AC-3) for KP 35, KP 36 & KP 34, KP 35, KP 36, KP 37 Boiler Version
- Contact Load, Silver: 4 A at 440 V (AC-15) for KPI 35, KPI 36, KPI 38
- Contact Load, Silver: 6 A at 440 V (AC-3) for KPI 35, KPI 36, KPI 38
Environmental Protection
- IP22
- IP30 - Unit Must be Mounted on a Flat Surface / A Flat Fitting & All Unused Holes Covered
- IP44 - Mounted as IP30 Plus Fitting of Top Cover
- IP55 - Unit Mounted in a Special IP55 Enclosure
Fluid
- Fresh Water - for Dual Pressure Switch
- Liquid - for KPI 35, KPI 36 & KPI 38, KP 34, KP 35, KP 36, KP 37 Boiler Version
Materials of Construction
- Copper Tin Alloy for Dual Pressure Switch - Bellows
- Free-Cutting Steel (Nickel-Plated) for KP 35, KP 36, KPI 38, KP 34, KP 35, KP 36, KP 37 Boiler Version & Dual Pressure Switch - Pressure Connector
- Gold - Contact Material
- Gold-Plated - Contact Material
- Phosphor Bronze for KP 35, KP 36, KPI 35, KPI 36, KPI 38 & Dual Pressure Switch - Bellows
- Polyethylene - Protective Cap
- Silver - Contact Material
- Stainless Steel for KP 35, KP 36 & KP 34, KP 35, KP 36, KP 37 Boiler Version - Bellows
Media
- Air - for KP 34, KP 35, KP 36, KP 37 Boiler Version
- Gas - for KP 35, KP 36 KPI 35, KPI 36 & KPI 38, KP 34, KP 35, KP 36, KP 37 Boiler Version
- Steam - for KP 34, KP 35, KP 36, KP 37 Boiler Version
Mounting
- Angle Mounting Bracket for KP
- Wall Mounting Bracket for KP
Operating Pressure
- psi: 246.6 to 435.1 (kPa: 1,700 to 3,000, bar: 17 to 30) - Permissible
Process Temperature
- -40° to 100° C (-40° to 212° F)
Set Point - Decreasing
- 0° to 150° C (32° to 302° F) - Thermostat, Typicals KP 75 to KP 81
- bar: -0.2 to 28
- kPa: -20 to 2,800
- psi: -2.90 to 406.1
Set Point - Increasing
- 0° to 150° C (32° to 302° F) - Thermostat, Typicals KP 75 to KP 81
- bar: -0.2 to 28
- kPa: -20 to 2,800
- psi: -2.90 to 406.1
Vibration
- 0 to 1,000 Hz at 4 G (1 G = 9.81 m/sec²)