Electromagnetic Flowmeter WaterMaster
Brand: ABB GroupWaterMaster's performance adheres to the most stringent global industry standards and is certified to key international approvals.
Proven in the toughest applications, Its rugged, robust and buriable sensors eliminate the need of expensive meter chambers.
Thereby, WaterMaster flowmeters provide a long, productive and maintenance-free asset life.
Take advantage of its innovative and versatile attributes to achieve interoperability within a wide range of asset management systems.
Features- OIML R49 and MID approved
- Superior control through advanced sensor design
- Submersible and buriable installation options
- Improved performance through digital signal processing (DSP)
- Intuitive navigation and configuration
- Speed, ease and security in the field
- Detailed diagnostics for rapid decision making
- Sensor size ranges: Full-bore FEV DN40 to 200 mm (11/2 to 8 in.), FEW DN10 to 2400 (3/8 to 96 in.), FEF DN250 to 600 (10 to 24 in.) / reduced-bore FER DN40 to 600 (11/2 to 24 in.)
Specifications
Brand
Power Supply: Mains
- 85 to 265 Vac @ < 7 VA
Power Supply: Low Voltage
- 24 Vac +10 % /-30 % @ < 7 VA
Power Supply: DC
- 24 V ± 30 % @ < 0.4 A
Digital Outputs
- Rating 30 V @ 220 mA, open collector, Galvanically isolated*
- Maximum output frequency 5250 Hz
- 1 off Dedicated to Alarm / Logic, Programmable function
- 2 off configurable to Either Pulse / Frequency or Alarm/Logic function
Current Output – HART FEX100 Variant
- 4-20 mA or 4 to 12/20 mA, Galvanically isolated*
- Maximum loop resistance 750 W
- Signal levels compliant with NAMUR NE 43 (3.8 to 20.5 mA)
- Low Alarm 3.6 mA, High Alarm 21.8 mA
- HART Protocol Version 5.7 (HART registered)
Additional Accuracy
- ± 0.1 % of Reading
- Temperature coefficient: typically < ± 20 ppm/°C
RS-485 Communications – PROFIBUS FEX100-DP Variant
- 3 Concurrent MS2 master Connections
- FEX100-DP Specific ident: 3431
- Standard idents: 9700, 9740, 9741
- PA Profile 3.01
- Registered name: FEX100-DP
- RS-485 (9.6kbps to 1.5Mbps), Galvanically isolated
- DPV0, DPV1
RS-485 Communications – Modbus FEX100-MB Variant
- Modbus RTU Protocol
- RS-485 (9.6kbps to 115.2 kbps), Galvanically isolated
Electrical Connections
- 20 mm Glands 1/2 in. NPT, 20 mm armored Glands
Temperature Limitations
- Ambient Temperature -20° to 60° C (-4° to 140° F)
- Temperature coefficient Typically < ± 10 ppm/°C @ Vel ³0.5 mls
Environmental Protection
- Humidity: 0 to 100 %
- Rating: IP67 (NEMA 4X) to 1 m (3.3 ft.) depth
Tamper-Proof Security
- Write access prevented by internal switch combined with external security Seals for MID applications
Languages
- English, French, German, Italian, Spanish, Polish
Infrared Service Port
- USB Adapter (Accessory), USB 1.1. and 2.0 compatible
- Driver Software for Windows® 2000, XP, 7 (32-bit) and Vista
Housing Material
- Powder-Coated Aluminium with Glass Window
Paint Specification
- Paint Coat ³70 μm thick RAL 9002 (Light grey)
Transmitter Vibration Testing
- Vibration Level: 7 m/s²
- Frequency Range: 20 to 150 Hz
- No. of sweeps in 3 orthogonal planes: 20
- Undetectable shift in transmitter Span or zero performance
Documentation
Brochure
User Manual
- HART Field Device Specification - WaterMaster FEX100 pdf 1.7 MB
- Manual - Diagnostic and Flow-Profiling Software for ABB Flow Meters ScrewDriver pdf 2.0 MB
- PROFIBUS FEX100-DP Parameter Tables -WaterMaster Electromagnetic Flowmeter pdf 721 KB
- User guide - F, V, W Series Electromagnetic flowmeter Full-bore flow sensors pdf 1.9 MB
- User guide - WaterMaster FET100 Electromagnetic flowmeter transmitter Hazardous areas ATEX IECEx areas 2, 21 and 22 pdf 3.9 MB