TI 180 E Electric Motor Protection Relay

Brand: Danfoss

Electronic motor protection relays TI 180 E give effective protection of electric motors exposed to thermal overload, phase failure and asymmetrical load. They therefore fulfil the requirements of IEC 947-4 and IEC 255-8.

TI 180 E are compact units with built-in current transformers for the measurement of motor operating current.
Features
  • Trip range 20 to 180 A, that can be reduced by loop to 2.5 to 5 A or less
  • Trip range from 160 to 630 A
  • Galvanically isolated signal contact
  • Light emitting diodes for operating and protection functions
  • Connection for thermistor over temperature protection
  • TI 180 E can be mounted on backplate, 35 mm symmetrical DIN rail or direct on contactors CI 110-180 via bus bars
  • Test and reset functions

4 models matching criteria
  • Control Voltage - 380-400 V, 50/60 Hz
100+ In Stock
$560.00CAD
Does not ship to United States
  • Control Voltage - 110 V, 50/60 Hz
50+ In Stock
$940.00CAD
Does not ship to United States
  • Control Voltage - 240 V, 50/60 Hz
50+ In Stock
$908.00CAD
Does not ship to United States
  • Control Voltage - 220-230 V, 50/60 Hz
20 In Stock
$1,030.00CAD
Does not ship to United States

Specifications

Brand

Ambient Temperature Range

  • -20° to 70° C (-4° to 158° F) - for Intermittent Operation
  • -5° to 60° C (23° to 140° F) - for Operation

Approvals & Certifications

  • EN 60947
  • AS
  • BS
  • BV
  • CE
  • CSA
  • IEC 255-4, 255-6, 255-8, 947-4, 947-5
  • LRS
  • PTB
  • SEV
  • UL
  • VDE 0660

Cable Length

  • 0 to 3,281 feet (0 to 1,000 metres)

Consumption

  • 2 W - for DC
  • 2.5 VA / 2 W - for AC

Current

  • 10 A, 500 V - Max.
  • 16 A, 250 V - Max.
  • 20-180 A - Setting Range
  • 4 A - Max.

Electrical Connectors

  • 4 to 95 mm² for Main Circuit
  • Cross Section: 0.5 to 2.5 mm²
  • Single Core: 2 x 0.75 to 2 x 2.5 mm² for Control Circuit
  • With Core Sleeve: 2 x 0.75 to 2 x 1.5 mm² for Control Circuit

Electrical Contacts

  • Normally Closed & Normally Open

Environmental Protection

  • IP54

Humidity

  • 83 % Relative Humidity, 23° C (73.4° F) - Temperature Climate
  • 92 % Relative Humidity, 40° C (104° F), 56 Days
  • 93 % Relative Humidity, 40° C (104° F) - Temperature Climate

Indication

  • LED Flash for Thermal Overload

Mounting

  • Direct Mounting
  • Panel Mount

Power

  • AC: 4.5 VA / 4 W - Max.
  • DC: 4 W - Max.

Relay Output

  • 24-440 V

Resistance

  • ≤ 15 ohms - Activation Value on Short-Circuit in Sensor Circuit at UA = -20° to 70° C (-4° to 158° F)
  • 1.8 kiloohms - Reset Value at UA = -20° to 70° C (-4° to 158° F)
  • 3.3 kiloohms - Activation Value at UA = -20° to 70° C (-4° to 158° F)
  • Maximum
  • Remote Reset: 22 kiloohms, 10 W - External Resistance for 240-440 V
  • Remote Reset: 8.2 kiloohms - External Resistance for 110-230 V

Rotation

  • 360° - Mounting Direction

Sensor / Probe Type

  • PTC
  • Thermistor

Shock

  • 30 G, Shock Pulse 11 milliseconds, Half-sinusoidal, in 3 Directions (x,y,z) as Per IEC 68-2-27/DIN 40046/7

Storage Temperature

  • -50° to 60° C (-58° to 140° F)
  • -50° to 85° C (-58° to 185° F) - Transport

Supply Voltage

  • 1,000 V - Nominal Voltage for Main Circuit
  • 2.5 kVac for 1 Minute - Test Voltage for Control Circuit as Per IEC 947-5
  • 2.5 kV, 1 MHz, 2 seconds - Noise Voltage
  • 240-600 V - Nominal Voltage for Control Circuit
  • 24-415 V at 50/60 Hz - Control Ciruit
  • 3.5 kVac for 1 Minute - Test Voltage for Main Circuit as Per IEC 947-4
  • 5 kV, 1.2/50 microsecond - Pulse Voltage

Vibration

  • 3 G at 10 to 150 Hz as Per IEC 68
show more