Approvals & Certifications
- ATEX Hazard Zone 2
- UL (C,US)
Capacity
- Rated Capacity: 2.8 to 8.6 KW
Flow Rate
- 1.7 to 2.8 Kv (m³/hour) with Offset 0.6 bar
- 2.5 to 8 Kv (m³/hour) With, Max.
Materials of Construction
Operating Pressure
- psi: 261 (kPa: 1,800, bar: 18) - Max.
Pressure Drop
- psi: 1.45 to 8.702 (kPa: 10 to 60, bar: 0.1 to 0.6)
Pressure Range
- Factory Setting: psi: 29 (kPa: 200, bar: 2)
- Maximum
- psi: 0 to 79.77 (kPa: 0 to 550, bar: 0 to 5.5) - Regulating Range
Process Temperature
- -45° to 130° C (-49° to 266° F)
Proof Pressure
- psi: 287.2 (kPa: 1,980, bar: 19.8) - Max.
Temperature Range
- Evaporating Temperature: -35° to 20° C (-31° to 68° F)
Tube Connection
- 1/2” Tube
- 1-1/8” Tube
- 1-3/8” Tube
- 5/8” Tube
- 7/8” Tube