Linearity
- ± 0.5 % of Full Scale
- ± 1 % of Full Scale
Operating Temperature
- -20° to 70° C (-4° to 158° F)
Burst Pressure
- psi: 24.65 (kPa: 170, bar: 1.7)
Compensated Temperature
- 2° to 54° C (35° to 129° F)
Adjustment
- Zero: ± 33 % of Full Scale
Tube Connection
- 1/4” Barbed Tube Fitting Male
Materials of Construction
- Cable Connection Socket: Nylon
- Polyester Foil (Front)
Span & Zero Effect
- Adjustment: ± 5 % of Full Scale
Temperature Coefficient
- Zero & Span: ± 0.06 %/K within 2° to 54° C (35° to 129° F), Reference Temperature 25° C (77° F)
Mounting
- DIN Rail
- Panel Mount
- Wall Mounted
Media
- Clean, Dry Air
- Non-Corrosive Dry Gases
Proof Pressure
- psi: 14.5 (kPa: 100, bar: 1)
Storage Temperature
- -40° to 90° C (-40° to 194° F)
Repeatability
- ± 0.5 % of Full Scale
- ± 1 % of Full Scale
- ≤ ± 0.1 % of Full Scale
Accuracy
- ± 0.5 % of Full Scale
- ± 1 % of Full Scale
Sensor, Probe Material
- Sensor: Aluminum
- Sensor: Glass
- Sensor: Silicon
Stability
- ≤ 0.5 % of Full Scale Per Year
Hysteresis
- ± 0.5 % of Full Scale
- ± 1 % of Full Scale
Humidity
- 10 to 90 % Relative Humidity, Non-Condensing
Approvals & Certifications
- CE EN 61000-4-2, EN 61000-4-3
- RoHS
Supply Voltage
- 19-36 Vdc (Nominal 24 Vdc)
- Nominal 24 Vdc
Electrical Connectors
- 1/2” Female DIN Cable Conduit
- PG9 Cable Gland
- Screw Terminal