Accuracy
- 0.01 % of Full Scale or ± 1.27 mm, whichever is greater
Repeatability
- ± 0.005 % of Full Scale or 0.31 mm (0.012 in), Whichever is Greater
Non-Linearity
- ± 0.01 % of Full Scale or 0.86 mm (0.034 in), Whichever is Greater
Process Pressure
- Up to 165.48 bar (2,400 psig)
- Standard -1 to 124.1 bar (-14.7 to 1,800 psig)
Process Temperature
- -195.5° to 426.6° C (-320° to 800° F)
Enclosure/Body Material
- Enclosure: Cast Low Copper Aluminum with Powder Coat
- Enclosure: 316/L Stainless Steel
Supply Voltage
- 9.0-32 Vdc for FOUNDATION Fieldbus
- 12-43 Vdc for 4-20 mA HART Loop Powered
Ambient Temperature
- -40° to 85° C (-40° to 185° F)
Humidity
- 0 to 100 % Relative Humidity
Remote Transmitter
- Standard Remote Distances of 5 m (16 ft), 10 m (33 ft), 20 m (66 ft), 30 m (98 ft)
Certifications & Approvals
- INMETRO
- NEPSI
- ATEX/IECEx
- EAC
- KOSHA
- FM
- SIL 2/3
Material of Construction
- Device Tag: AISI 316 Stainless Steel
- Sensor Tube: 316/L Stainless Steel, Alloy 20, Hastelloy C-276, PFA-Teflon Jacketed
Probe Length
- 22.86 m (75 ft) Max. w/ W7 Flexible Probe in Sensor Well
- 304.8 to 9.14 m (1 to 30 ft)
Mounting
- 3/4” MNPT Compression Fitting
- Plugs, Threaded Fittings, Loose Flanges and Welded Flange Process Connections Also Available