AME 110 NLX Modulating Control Actuator

Brand: Danfoss

The actuators are used together with automatically balanced combination valve type AB-QM for DN 10 to DN 32. 

The actuator can be used with fan coil units, induction units, small reheaters, recoolers and zone  applications in which hot/cold water is the controlled medium.

Specifications

Brand

Actuator Type

  • Modulating Control

Ambient Temperature Range

  • 0° to 55° C (32° to 131° F)

Applications

  • Fancoils / Induction Units
  • Overload Preventing System
  • Recoolers
  • Small Reheaters

Approvals & Certifications

  • EN 60730-1
  • EN 60730-2-14
  • EN 61000-6-1
  • EN 61000-6-3

Approvals & Certifications

  • CE
  • EMC Directive 2004/108/EEC
  • Low Voltage Directive (LVD) 2006/95/EC

Cable Length

  • 4.92 to 32.81 feet (1.5 to 10 metres)

Consumption

  • Power Consumption (Running): 1.5 VA
  • Power Consumption (Standby): 0.4 W

Electrical Connectors

  • Halogen Free Cable

Environmental Protection

  • IP42

Frequency

  • 50/60 Hz

Input

  • Control Input: 0-10 V (2-10) V
  • Control Input: 0-20 mA (4-20)mA

Media

  • Hot/Cold Water

Mounting Position

  • Horizontal or Stem Pointing Upwards

Output

  • Control Output: 0-10 V

Process Temperature

  • Maximum

Resistance

  • Input Resistance: 500 ohms
  • Input Resistance: 200 kiloohms
  • Output Resistance (Min.): 38 kiloohms

Storage Temperature

  • -40° to 70° C (-40° to 158° F)

Supply Voltage

  • 24 Vac ± 20 %

Switch Type

  • DIP Switches

  • Fancoils / Induction Units
  • Overload Preventing of Actuator & Valve
  • Small Reheaters
  • Recoolers

show more