Available Voltage Range
- IP20: 110-120 V, 500-600 V
- IP66: 110-120 V, 200-240 V, 380-480 V, 500-600 V
Control Mode
- V/Hz and open loop vector
Overload Capacity
- Drive output 150 % for one minute and 175 % for 2 seconds
Maximum Load
- IP20: 1.5 HP @ 120 V In/230 V Out, 20 HP @ 600 V In/Out
- IP66: 5 HP @ 230 Vac, 10 HP @ 460 Vac, 15 HP @ 600 Vac
Input Voltage
- IP20: 115 Vac (99-126), 600 Vac (450-660)
- IP66: 230 Vac (198-264), 460 Vac (342-528)
Frequency
- Rated Input 50/60 Hz (± 5 %)
- Control Range: 0-500 Hz
Operating Temperature
- IP20: -10° to 50° C
- IP66: -10° to 40° C
Communication
- Built-in Modbus-RTU (RS-485)
Certifications & Approvals
- UL, cUL, CE, C-tick, GOST
Altitude
- 1,000 m (3,300 ft), derate by 1 % per 100M up to 2,000 m Max.
Ambient Temperature
- -10° to 50° C (14° to 12° F)
Storage Temperature
- -40° to 60° C (-40° to 140° F)
Humidity
- 10 % to 95 % Relative Humidity, Non-Condensing