- Range - 0.02 to 10 ppm Mn
- Number of Streams - Measuring 3 Streams
- Communication - None
- Enclosure - Standard
- Power Supply - 18 to 36 Vdc
- Manual - Spanish
- Certification - None
Specifications
Brand
Measurement Range
- 0.02 to 10 ppm Mn (0.02 to 10 mg/L)
Accuracy / Maximum Measured Error
- ± 7 % of Reading or ± 0.005 ppm for 5 to 10 ppm, whichever is greater
- ± 5 % of Reading or ± 0.005 ppm for 0 to 5 ppm, whichever is greater
Repeatability
- ± 5 % of Reading or ± 0.005 ppm, whichever is greater
Resolution
- 0.001 ppm or 1 ppb
Calibration
- 2-Point, Automatic Calibration
Operating Temperature
- 5° to 45° C (41° to 113° F)
Sample Temperature
- 1° to 40° C (32° to 104° F)
Sample Pressure
- 5 psi Max.
Flow Rate
- Sample: Continuous 200 to 500 mL/min
Humidity
- Up to 95 % Relative Humidity, Non-Condensing
Display
- Color, TFT, LCD with built-in backlight and brightness Adjustment
Environmental Protection
- IP 31
Materials of Construction
- Door: Acrylic
- Lower Tray: 20 % Glass-loaded Polypropylene
- Main Enclosure: Noryl
- Electronics Enclosure: 10 % Glass-loaded Polycarbonate
Power Supply
- 18-36 Vdc optional
- 100-240 Vac Max. 50/60 Hz ± 10 %
Power Consumption
- 100 W Max. - DC
- 75 W Max. - AC
Certifications & Approvals
- EMC
- CE
- cULus
- LV Directives
Communication
- PROFIBUS DP V1.0
Documentation
Brochure
- Course description - Z206e Aztec600 | External version pdf 48 KB
- Course description - Z253e Continuous Water Analyzer (CWA) Range | External version pdf 49 KB
- Security advisory – DataManagerPro file permissions escalation vulnerability | ABB-VU-PAMP-089290 pdf 23 KB
- Version matrix - AW630 pdf 11 KB