Price
$1,032.00
CAD
Stock
50+ In Stock
- Range - 0 to 500 Hazen
- Number of Streams - Measuring 3 Streams
- Communication - Profibus DP V1.0
- Enclosure - Standard
- Power Supply - 18 to 36 Vdc
- Manual - Italian
- Certification - Certificate of Calibration
Specifications
Brand
Measurement Range
- 0 to 500 Pt-Co units (0 to 500 Hazen units)
Measurement Frequency
- 1 to 12 measurements per hour
Accuracy / Maximum Measured Error
- < ± 2 % of Reading or ± 0.5 Hazen for 0 to 300 Hazen (Whichever is the greater)
- < ± 5 % of Reading for 300 to 500 Hazen
Repeatability
- < ± 1 % of Reading (At 20 % of Span)
Resolution
- 0 to 10 Hazen - 0.01 Hazen
- 10 to 100 Hazen - 0.1 Hazen
- 100 to 500 Hazen - 1 Hazen
Calibration
- 2-Point, Automatic Calibration
Operating Temperature
- 5° to 40° C (41° to 104° F)
Humidity
- Up to 95 % RH, Non-Condensing
Sample Temperature
- 1° to 40° C (32° to 104° F)
Sample Flow
- Continuous, 200 to 500 mL/min
Sample Pressure
- 5 psi Max.
Display
- 76800 Pixel Display
- Color, TFT, LCD with built-in backlight and brightness Adjustment
Environmental Protection
- IP 31
Process Conenction
- Sample Connections - Inlet: 6 mm O.D. push-fit x 1/4" BSP elbow
- Sample Connections - Outlet: 10 mm O.D. push-fit x 3/8" BSP elbow
Material of Construction
- Door: Acrylic
- Main Enclosure: Noryl
- Electronics Enclosure & Lower Tray: 10 % Glass-loaded Polycarbonate
Power Supply
- 18-36 Vdc (Optional)
- 100-240 Vac Max. 50/60 Hz ± 10 % (90-264 Vac, 45/65 Hz)
Power Consumption
- 100 W Max. - DC
- 75 W Max. - AC
Communication
- PROFIBUS DP V1.0
Certifications & Approvals
- cULus Listed
- CE Mark
- EMC