Endura AZ30 Combustion Gas Oxygen Analyzer
Brand: ABB GroupThe Endura AZ30 is an explosion-proof / flameproof combustion gas analyzer system designed for use in hazardous areas.
The sensor, based on a zirconium oxide cell, is mounted at the tip of the probe that is inserted in the flue duct.
The resulting direct, in situ measurement provides accurate and rapid oxygen reading for combustion control optimization and emissions monitoring.
Specifications
Brand
Certifications & Approvals
- ATEX / IECEx
- CE Mark
- cFMus
Environmental Protection
- IP66
- NEMA 4X
Measurement Range
- 0 to 20.95 % O₂ Max.
Response Time
- Test Gas: initial dead time 3 s, T90 < 10 s
Accuracy
- < ± 0.75 % of Reading or 0.05 % O₂
Drift
- < ± 0.2 % Typical
- < ± 1 % Max. % O₂ Range value per month (Without calibration)
Operating Temperature
- Probe: -20° to 70° C (-4° to 158° F) (Hazardous area certification is valid only between -20° and 70° C [-4° and 158° F])
- Transmitter: -20° to 55° C (-4° to 131° F)
Process Temperature
- All probe: -20° to 800° C (-4° to 1,472° F)
Storage Temperature
- -40° to 85° C (-40° to 185° F)
Humidity
- Up to 95 % Relative Humidity, Non-Condensing
Power Supply
- Probe Heater: < 100 W
- Electronics: < 10 W
- Maximum Current 1.2 A
- 100-240 Vac ± 10 %, 50/60 Hz
Insertion Length
- Probe: 0.5 to 2.0 m (1.7 to 6.6 ft)
Process Connection
- JIS B2238 5K
- DIN 2501 Part 1
- ANSI B16.5 150 lb
Body Material
- Probe: 316L Stainless Steel
Mounting
- Horizontal to Vertically down
Material of Construction
- Remote transmitter: Aluminum
- Remote terminal housing: 316L Stainless Steel
- Integral transmitter: Aluminium transmitter housing / Stainless Steel probe and terminal housing
Documentation
Brochure
- Brochure - Endura AZ30 combustion gas O2 analysis | Rugged, stable operation even in hazardous applications pdf 2.7 MB
- Brochure - Endura combustion gas analyzers | More stability. Less worry. Tough made easy pdf 5.4 MB
- Course description - Z229e Endura Combustion Gas Analyzers | External version pdf 48 KB
- Version matrix - AZ20 / AZ25 / AZ30 | Endura pdf 28 KB
- Supplementary information - Driver AZ20 / AZ25 / AZ30 HART | Endura pdf 54 KB
Certificate
- Certificate - Government of India, Ministry of Commerce and Industry Petroleum and Explosives Safety Organisation (PESO) Approval of AZ30 O2 Transmitter under Petroloeum Rules, 2002 pdf 82 KB
- Certificate of compliance - FM - Hazardous (Classified) Location Electrical Equipment pdf 66 KB
- Certificate of compliance for electrical equipment per Canadian requirements - FM Approvals pdf 64 KB
- Certificate of conformance - AZ30 - Ex-proof equipment (GOST) pdf 6.3 MB
- Certificate of conformity - AZ30 Oxygen probe | IECEx Certificate of Conformity pdf 1.9 MB
- Certificate of conformity - AZ30 Oxygen Probe | IECEx Certificate of Conformity pdf 151 KB
- Certificate of conformity - AZ30 Oxygen Transmitter | IECEx Certificate of Conformity pdf 1.7 MB
- Certificate of conformity - AZ30 Remote Terminal Box. IECEx Certificate of Conformity pdf 148 KB
- EC declaration of conformity - AZ30 Oxygen Probe pdf 291 KB
- EC declaration of conformity - AZ30 Oxygen Transmitter pdf 295 KB
- EC declaration of conformity - AZ30 Remote Terminal Box pdf 292 KB
- Examination certificate - AZ30 Oxygen Transmitter. EC - Type pdf 148 KB
- Supplementary EU - Type Examination Certificate | AZ30 Oxygen Probe pdf 1.2 MB
- Examination certificate - AZ30 Oxygen Probe. EC - Type pdf 152 KB
- Examination certificate - AZ30 Remote Terminal Box. EC - Type pdf 124 KB