Ambient Temperature Range
- 90° C (194° F) for Sensors without Temperature Transmitter
Connection Material
- 316L Stainless Steel, 1.4401
Electrical Connectors
- DIN 43763
- Silicone Cable
- Terminal Block
Environmental Protection
- IP65 According to IEC 60529
Flow Rate
- 25 m/sec - Permissible Media Velocity for Air, Steam
- 3 m/sec - Permissible Media Velocity for Water
Insertion 'U' Length
- 1.9” to 9.8” (50 to 250 mm)
Length
- 1.97” (50 mm) - Extension Length
Materials of Construction
- 316Ti Stainless Steel, 1.4542 - Protection Tube & Extension Length
Measuring Range
- -50° to 200° C (-58° to 392° F)
Media
- Air
- Liquids & Gases
- Oil
- Steam
- Water
Output
- 4-20 mA - Temperature Transmitter MBT 9110
Response Time
- 110 to 390 seconds for Air 1 m/sec
- 14 to 42 seconds for Water 0.2 m/sec
Sensor / Probe Connection
Shock
- 100 G, 6 milliseconds - Vibration Stability
Supply Voltage
- 8-35 Vdc - Temperature Transmitter MBT 9110
Temperature Range
- -50° to 200° C (-58° to 392° F)
- 85° C (185° F) for Sensors with Temperature Transmitter
Tolerance
- EN 60751 Class B: ± (0.3 + 0.005 x T), T = Temperature of Medium, Numerical Value
Vibration