AVPQ 4 Differential Pressure & Flow Controller

Brand: Danfoss

AVPQ 4 is a self-acting differential pressure and flow controller primarily for use in district heating systems. The controller closes on rising differential pressure or when set max. flow is exceeded.

The controller has a control valve with adjustable flow restrictor, an actuator with two control diaphragms and handle for differential pressure setting.

Specifications

Brand

Actuator Size

  • 8.37 in² (54 cm²)

BSP Connection

  • G 1” A
  • G 1-1/4” A
  • G 1-3/4” A
  • G 2” A
  • G 2-1/2” A
  • G 3/4” A

Cone Material

  • Dezincing Free Brass CuZn36Pb2As

Diaphragm Material

  • EPDM

Differential Pressure

  • psi: 232.1 (kPa: 1,600, bar: 16) - Max.
  • psi: 290.1 (kPa: 2,000, bar: 20) - Max.

Enclosure, Body Material

  • Lower Casing of Actuator: Dezincing Free Brass CuZn36Pb2As
  • Upper Casing of Actuator: 304L Stainless Steel
  • Valve (Thread & Flange): Ductile Iron EN-GJS-400-18-LT (GGG-40.3)
  • Valve (Thread): Red Bronze CuSn5ZnPb (Rg5)

Flange Size - 1-1/2” (DN 40)

  • 1-1/2” (DN 40) - PN 25 According to EN 1092-2

Flange Size - 1-1/4” (DN 32)

  • 1-1/4” (DN 32) - PN 25 According to EN 1092-2

Flange Size - 2” (DN 50)

  • 2” (DN 50) - PN 25 According to EN 1092-2

Flow Rate

  • 0.01 to 14.71 scfm (0.015 to 25 m³/hour)

Materials of Construction

  • Impulse Tube: Copper

Media

  • Circulation, Glycolic Water Up to 30 %, pH: 7 to 10

Nominal Pressure

  • psi: 362.6 (bar: 25, kPa: 2,500)

Process Temperature

  • 2° to 150° C (35.6° to 302° F)

Seat / Seal Material

  • Sealing: EPDM
  • Valve Seat: 316Ti Stainless Steel

  • District heating systems
show more